What is the proper way to manage cabling behind patch panels?

5,732

I like to use 1U front and rear cable management above and below my patch panels. This mostly applies to 2-post installs... As for the cabling bundle, it should be secured zip-tied and routed appropriately...

enter image description here

However, a 4-post example from my past...

Size the run, bundle with slack, secure along the side of cabinet...

enter image description here

enter image description here

Share:
5,732

Related videos on Youtube

alx9r
Author by

alx9r

Updated on September 18, 2022

Comments

  • alx9r
    alx9r almost 2 years

    I have a 4-post 19" rack with a 72-port 2U quickport patch panel where horizontal structured cabling terminates. The cables are bundled and enter the rack at the rear. From the back of the rack, they need to

    1. get near the front of the rack directly behind the patch panel,
    2. fan out to the whole width of the patch panel, and
    3. somehow have enough slack so that they can be terminated.

    What is the proper way to accomplish this?

    How should the bundle of cable be supported on its way from the rear to the front of the rack?

    What considerations determine the ideal distance from the front of the rack to begin fan out?

    How can I prevent droop in the fanned-out section directly behind the patch panel from interfering with the rack unit below?

    • ewwhite
      ewwhite almost 12 years
      Do you have a photo? Are you doing this on a 2-post telco rack or a 4-post unit?
    • alx9r
      alx9r almost 12 years
      It is a 19" 4-post rack. I don't have a photo handy but I could take one. What should the photo show?
    • voretaq7
      voretaq7 almost 12 years
      In an ideal world you avoid this problem entirely by using something like Panduit's DataPatch panels which are RJ21 on the back and RJ45 on the front -- No need to fan out or fiddle with punchdown blocks. This may not help in your situation where you already have the panel, though you can consider it for next time.
    • alx9r
      alx9r almost 12 years
      @voretaq7 - The patch panel I'm using is a quickport panel not 110-style, so I don't think I'm any worse off with what I have than the panduit patch panel you suggest. Even with quickports or that panduit panel, you still have to fan-out from a bundle to individual cables.
    • voretaq7
      voretaq7 almost 12 years
      @user115232 With the panel I linked to you do not fan out cables - the connection is a single bundle to a single RJ21 connector and all the fanning/punching is inside the panel and already done for you at the factory. QuickPort connectors are much nicer than 110 blocks, but still require you to pull the cable apart and punch it (albeit with the connector itself doing most of the work for you). The downside to the RJ21 style panel is that a dead port means replacing the whole run, but how often do you break trunk cables?
    • alx9r
      alx9r almost 12 years
      @voretaq7 Oops, I was confused about what an RJ21 connector is. I'm not dealing with trunk cables here though, I am terminating 50+ cat5e drops, how would those get terminated as an RJ21?
    • voretaq7
      voretaq7 almost 12 years
      @user115232 the usual way is to get a custom cable made up, or use a "hydra cable" which breaks out to RJ45 (usually male) -- unfortunately the RJ21-style panels are really more designed for datacenter cable distribution than endpoint termination so they don't completely eliminate the problem, they just help reduce the number of wires traveling through the floor & the amount of fanned/stripped wire you have to deal with.
  • voretaq7
    voretaq7 almost 12 years
    ...velcro tied (you heathen! :-)
  • alx9r
    alx9r almost 12 years
    @ewwhite - thanks for the updated answer. Did you install that side rail that you have strapped the bundle to for this purpose? The only side rails I have are riveted in place and many rack units above or below my patch panel.
  • Ryan Ferretti
    Ryan Ferretti almost 12 years
    Great answer, and love the use of the pictures (especially the hard to get side view. And I agree you are a heathen for using zip ties.
  • ewwhite
    ewwhite almost 12 years
    @user115232 The side rail in that rack is structural. I understand that ever rack is different, so your path/approach may need to be modified. I generally try to avoid terminating site wiring in an enclosure because it can get very messy in the long run.
  • Chef Flambe
    Chef Flambe almost 12 years
    Love how clean you did it. I've seen so many gong shows over the past few years it's really nice to see examples of work well done.